Tell CME the conductor material (copper, aluminum), cross-section, conductor type (solid, stranded), and the bolt/busbar hole size. We'll help you select the right lug and tool, and prepare a B2B quote.
Send a quote request →Sheet metal or tube — it isn't a matter of preference
"Crimp cable lug" and "compression cable lug" describe two different constructions, not two words for the same thing. A crimp lug (DIN 46234 type) is made from copper sheet rolled and soldered along a seam — intended for stranded conductors (not solid wire), closed with an indent-crimping tool. A compression lug (DIN 46235 type) is made from copper tube — it accepts solid, stranded, and fine-stranded conductors, and is closed with a hexagonal die, usually in a hydraulic press. Mixing up the two types, or using the wrong tool for a given type, produces a joint that doesn't meet the pull-out strength specified by the test standard.
Standards by construction and cross-section
| Standard | Construction | Cross-section | Tool |
|---|---|---|---|
| DIN 46234 | Cu sheet, soldered seam | 0.5–240 mm² | Indent crimper |
| DIN 46235 | Cu tube | 6–1000 mm² | Hex-die press |
| DIN 46329 | Al tube, with compound | 10–1000 mm² | Hex-die press |
Cross-sections per manufacturer datasheets (the range can vary between suppliers). CME's standard production covers 10–400 mm² — larger cross-sections on request.
Why you can't swap the tool
An indent die and a hexagonal die deform metal in completely different ways. Using an indent crimper on a tubular lug (DIN 46235) won't produce full, even compression around the tube's full circumference — gaps remain, letting moisture and oxygen into the joint and raising contact resistance over time. Using a hex press on a thin sheet-metal lug (DIN 46234) can deform or cut through it. The die selection (number and width) must match the specific lug — manufacturers mark this directly on the lug (number and width of crimps).
Aluminum needs a different lug than copper
Aluminum develops a non-conductive oxide layer the moment it contacts air — which is why aluminum lugs (DIN 46329) are never used without a filling compound containing an abrasive additive (corundum) that cuts through the oxide layer during crimping, then seals the joint against oxygen and moisture. Aluminum dies have a wider "bite" (approx. 7 mm, 2 mm wider than copper dies) for greater contact area. Copper lugs never substitute for aluminum ones on an aluminum conductor — doing so risks accelerated corrosion and loss of contact. Connecting aluminum to copper (e.g. a copper busbar to an aluminum conductor) requires a dedicated bimetal Al-Cu lug, not a standard lug made of either metal alone.
Treating DIN 46234 and DIN 46235 as two sizes of the same lug, differing only by cross-section. They're two different constructions (sheet vs. tube) requiring different crimping tools — the standard number on a lug's datasheet tells you which tool you need, not just which cross-section it handles. When ordering, always specify both: the lug type (standard) and the conductor material.
Test standards — IEC 61238-1
The electrical and mechanical properties of cable lugs (both crimp and compression types) are specified by IEC 61238-1. The standard defines, among other things: a pull-out strength test (the axial force at which the joint must not separate or the conductor pull free of the barrel), an electrical durability test (1000 cycles of heating the joint to 120°C, simulating in-service operation), and a current test at elevated temperature (up to 250°C). Compliance documentation for a specific part number is available on request.
What's available from CME
CME distributes cable lugs from Kardeş Elektrik (copper tubular lugs to EN 13600, standard production 10–400 mm²) and the full Simpa Elektrik range: crimp lugs in copper, aluminum, and bimetal Al-Cu, splice sleeves, busbars, and cable ferrules/terminals. Accessories are also available: mechanical and hydraulic crimping tools, crimping dies, cable cutters, and cable ties/clips.
Tool selection (mechanical vs. hydraulic, die number) depends on the specific lug — we confirm tool-to-lug compatibility with every quote request.
What to prepare for your quote request
- Conductor material: copper, aluminum, or an Al-Cu (bimetal) connection.
- Cross-section and conductor type (solid wire, stranded, fine-stranded).
- Bolt/mounting hole size (e.g. M8, M12).
- Whether you also need the crimping tool (mechanical or hydraulic).
- Planned quantity and delivery schedule.
Frequently asked questions
Can a crimp lug (DIN 46234) handle large cross-sections?
Catalog ranges go up to about 240 mm², but tubular lugs (DIN 46235) are more commonly used for larger cross-sections — check with CME which construction is available for your cross-section and application.
Can I use a copper lug on an aluminum conductor?
No — this risks accelerated corrosion of the contact and loss of conductivity over time. Aluminum conductors require dedicated aluminum lugs (DIN 46329) or bimetal Al-Cu lugs when connecting to copper components.
Does a crimping tool for copper lugs also work for aluminum ones?
Usually not directly — aluminum dies have a different bite width than copper dies. Confirm tool and die compatibility with CME before purchasing.
See also the full CME cable lugs category.