PVC and LSZH represent two different approaches to limiting fire risk, each optimized for different scenarios. A PVC jacket contains chlorine, which acts as a natural flame retardant — but when it burns, it releases hydrogen chloride (HCl) gas and dense black smoke. An LSZH jacket (typically a polyolefin with a high loading of mineral fillers, e.g. aluminum trihydrate, ATH) limits flammability physically, without chlorine — when it burns it produces far less smoke and releases no halogen acids. Which choice is right depends on where and under what conditions the cable will operate — not on which material is "more modern."
The tests that actually differentiate these materials
PVC and LSZH cables are evaluated against the same standards — they differ in results, not in the tests themselves. Below is the typical (not guaranteed for every specific construction) behavior of both materials:
| Standard | What it tests | Typical PVC | Typical LSZH |
|---|---|---|---|
| IEC 60332-1 | Flame on a single cable | Usually passes | Usually passes |
| IEC 60332-3 | Flame on a bundle | Depends on formulation | Higher categories easier |
| IEC 61034-2 | Smoke density (transmittance) | Typically approx. 20–40% | Typically ≥60% |
| IEC 60754-1 | HCl content in gases | Well above 0.5% | <0.5% (halogen-free) |
| IEC 60754-2 | pH and conductivity of gases | Acidic, low pH | pH >4.3 (class a1/a2) |
Indicative values based on industry publications comparing typical PVC and LSZH formulations — the actual result depends on the manufacturer's specific compound. For a given cable, always check the test certificate, not just the material name.
IEC 60332-1 — flame on a single cable
This is the baseline test that almost every cable sold in the EU must pass. A propane/air flame applied at a 45° angle is held against the sample for a duration that depends on its diameter (e.g. 60 s for a 25 mm cable). The cable passes if the flame does not spread more than 50 mm above the upper clamp and the damage does not extend below 540 mm from the upper clamp. This test only checks whether a single cable keeps burning on its own after the flame is removed — it says nothing about smoke or gas toxicity.
IEC 60332-3 — flame on a bundle of cables
In a real installation, cables run in bundles (trays, ladder racks) — and it's flame spread between cables in a bundle, not a single cable, that poses the greater risk. The test is performed on a vertical ladder rig with samples representing a defined quantity of non-metallic material per meter — the category determines the severity of the test:
| Category | Non-metallic material (l/m) | Fire load |
|---|---|---|
| A | 7.0 | High |
| B | 3.5 | Medium |
| C | 1.5 | Low |
| D | 0.5 | Very low (small cables) |
The higher the category (A is highest), the stricter the test — the cable must limit flame spread under a greater load of combustible material in the bundle.
IEC 61034-2 — smoke density
This is the test where the difference between PVC and LSZH is most visible. Cable samples (1 m in total) are placed in a 3 m³ chamber, and a flame from an alcohol source (1 l) is applied 70 mm below the sample. The test runs for up to 40 minutes or until light transmittance stabilizes. The result is reported as a percentage of transmitted light — 0% means complete obscuration, 100% means full clarity. LSZH cables are designed to maintain transmittance of at least approximately 60%, while typical PVC cables fall in the 20–40% range. In practice this means drastically different visibility in a smoke-filled room during evacuation.
IEC 60754-1 and -2 — acid gases and toxicity
IEC 60754-1 measures the content of halogen acids (mainly HCl) in the gases produced during combustion — the sample is heated to 800°C (40-minute ramp plus 20-minute hold) and the released gas is measured. A material is considered halogen-free when its HCl content is below 0.5% by mass. IEC 60754-2 measures the pH and conductivity of the same gases — class a1 requires pH above 4.3 and conductivity below 2.5 µS/mm, class a2 requires the same pH with conductivity below 10 µS/mm. PVC cables, due to their chlorine content, do not meet these thresholds — this is a natural consequence of the material's chemistry, not a defect in a specific product.
Euroclass ratings under EN 50575 (CPR)
Since July 2017, cables used in construction works within the EU fall under the Construction Products Regulation (CPR) and must carry a declared reaction-to-fire class. The base classes, from best to worst: Aca, B1ca, B2ca, Cca, Dca, Eca, Fca. Additional letters are appended for smoke (s1a/s1b/s2/s3 — s1 is split based on the IEC 61034-2 test result), flaming droplets (d0/d1/d2), and acidity (a1/a2/a3 — based on IEC 60754). A full designation looks like this: Cca-s1b,d1,a1. Telecommunications cables rarely exceed class B2ca; achieving a high base class with low additional letters (low s, d, a) is in practice much easier with an LSZH formulation than with PVC.
Assuming that the label "LSZH" on a datasheet or quote automatically means a specific Euroclass rating or specific transmittance/acidity values. LSZH describes a family of materials (halogen-free, low-smoke), not a certified performance class — two LSZH cables from different manufacturers (or even different constructions from the same manufacturer) can have different test results and different CPR classes. If a project requires a specific class (e.g. Cca-s1b,d1,a1 in a public building), always request the test certificate for the specific product code, not just confirmation that the cable is "LSZH."
When to choose LSZH, and when PVC
LSZH is typically required or strongly recommended in enclosed spaces with heavy human occupancy, where smoke and toxic gases pose a real evacuation hazard: public buildings, data centers, metro and rail transport, ships, tunnels. PVC remains a common, lower-cost choice for industrial, outdoor, and general-purpose installations where the risk of smoke accumulating in an enclosed, occupied space is lower — provided the locally required base class is met (e.g. Eca as the EU minimum).
What's available from CME
CME distributes low-voltage PVC power cables from NAK Kablo, as well as cables from Baran Kablo's fire-safety range — including HFFR and LSZH cables for alarm, control, and signal applications. Fire-resistant cables (which maintain circuit function during a fire) under the FE180/PH120 designation from Etabir/Birtaş are also available.
A fire-resistant cable (FE180/PH120, per IEC 60331/EN 50200) is a different category from a low-smoke, halogen-free (LSZH) cable — the former is designed to maintain circuit operation during a fire (e.g. for alarm systems), the latter limits smoke and toxicity during combustion. Some cables combine both properties, but don't assume this without confirming it in the documentation. We confirm the exact Euroclass rating and test results for a specific product code on request.
What to prepare for your quote request
- Installation location: public building, enclosed/ventilated space, industrial, or outdoor installation.
- The required Euroclass rating under EN 50575, if specified in the project.
- Cross-section, number of cores, and rated voltage of the cable.
- Operating temperature range and any additional requirements (fire resistance FE/PH, shielding).
- Planned quantity and delivery schedule.
Frequently asked questions
Is LSZH always a legal requirement?
Not always — it depends on the type of building and local/national regulations. However, many public buildings and public-use facilities in the EU require a specific Euroclass rating, which in practice is easier to achieve with an LSZH formulation. Check the project requirements or consult CME.
Is LSZH cable harder to install than PVC?
Some LSZH formulations can be somewhat less flexible than comparable PVC cables, though this varies between manufacturers and constructions. It's worth checking the datasheet for the specific product.
Is fire-resistant cable (FE180/PH120) the same as LSZH?
No — these are different properties. Fire-resistant cable maintains circuit operation during a fire; LSZH limits smoke and toxicity. Some products combine both features, but this must be confirmed separately.